- Contact Person : Ms. Wang Liz
- Company Name : Kinco Automation (Shanghai) Ltd.
- Tel : 86-21-68798588
- Fax : 86-21-68797688
- Address : Shanghai,Shanghai,2/F,Rm 102, Bldg. 1, No. 1387, Zhangdong Road, Zhangjiang Hi-tech Park
- Country/Region : China
- Zip : 201203
PLC CPU304EX
PLC(programmable logic controller) CPU304EX Technical Specification | |
Performance Indexes | CPU304EX |
K304EX-14AR | |
CPU | 16-bit industrial |
Execution Speed | Typical Bool instruction time: <0.5 μS Word operation time: <48μS Arithmetic operation time for integers: <65μS Arithmetic operation time for floating points: <150μS |
DI Points | 8XDC24V |
DO Points | 6Xrelay |
User Program Memory | FRAM, 8KB/about 1,200 steps |
Program Backup | Permanent storage, without the need of battery |
Memory Area | Variable storage area (V area): 4KB System storage area (SM area): 300 bytes Internal storage area (M area): 32 bytes |
Data Retention Characteristic | Configure with the programming software: V area, C (counter) area |
Retention Mode and Period | Adopt super capacitors and support a retention period of not less than 144 hours upon power failure under normal temperature. |
Data Backup Characteristic | Perform backup operations VB3648~VB3902 according to user instructions, 255 bytes in total |
Backup Mode and Time
| FRAM, 255 bytes in total (writing operation for 10 billion times), permanent backup |
Floating Points | Supported; the whole V area can be used for floating points |
Programming Language Supported | Ladder Drawing (LD), Instruction List (IL) |
Instruction Set | Basic instructions: 55; expansion instructions: 252 |
Password Protection | Yes |
Max. I/O | Digital data: 78 in total (64 DI and 64 DO respectively); Analog data: 16 in total (16 AI and 16 AO respectively) |
Counter | 128 |
Operation Mode of Counter | Addition, subtraction |
Counter Range | -32768~32767 |
Counting Value Retention Function | Yes |
Timer | 128 1 ms time base: 4 10 ms time base: 16 100 ms time base: 108 |
High-speed Counter | 6 high-speed counters where, single-phase counters: 6, with a maximum frequency of 30 KHz where, dual-phase counters: 4, with a maximum frequency of 20 KHz |
Pulse Output | 2, PTO (Pulse Train Output)/PWM (Pulse Width Modulation output); Maximum output frequency: 20 KHz |
Analog Potentiometer | 2, 10-bit resolution, values corresponding to internal registers |
Interruption Function | Timing interruption: 2, 1ms resolution; Timer interruption: T2/T3, 1ms resolution; Edge interruption: 4, rising edge or falling edge optional; High-speed interruption, communication interruption |
Real-time Clock | Yes, with an error not greater than 2 minutes/month under a temperature of 25°C The user can use the software to set/read: year, month, day, hour, minute, second, week. Standby batteries are used to supply power for the real-time clock upon power failure. Under normal temperature, the accumulative retention period of the real-time clock upon power failure is up to 50,000 hours. |
Number of Connectable Expansion Modules | 4; regardless of types |
COM Port | 1, RS232 or RS485; Supported working modes: Programming, Modbus-RTU (slave), Free protocol |
Equipment Connected with COM Port | RS232/RS485: PC (for programming), third-party HMI panel, third-party serial communication equipment (for example, instruments, bar code reader, etc.) |
Input Power Supply | AC85~265V |
Sensor Load Power Supply | DC24V, max. 500 mA |
Dimensions (L*W*H) | 125X114X70 |
PLC CPU304EX